Signal lamps Ø30 type NEF30-L or D30 with metal body and Ø22 type L22 or D22 with plastic bodies are designed to be built properly into Ø30,5 mm or Ø22,5 mm holes in consoles, control desk or in machines and equipment.
Signal lamps may be used my in various climate zone (N/2, W/3), in any position under roof in industrial conditions with environmental pollution degree 2.
In respect of luminous element signalling lamp can be devided into:
- signal lamp with bulbs,
- signal lamps with LEDS
Signal lamps are supplied as complete products in accordance with orders.
| PARAMETER | VALUE |
| Rated insulation voltage Ui | 250V |
| Rated voltage Ue | various |
| Type of emitting light element | bulb - BA7s max 2W - BA9s max 3W T6,8 max 2W LEDs - StarLED BA9s |
| Luminous intensiti - with bubls - with LEDs |
100...400 mcd 1000 mcd |
| Blinking frequency for blinking lamps | 1,4 - 2,8Hz |
| Power dissipation for lamps with resistor | max 8W |
| Protection degree: - part over console - part under console |
given by each type of lamp NEF30-L, L22: IP20 D30, D22: IP00 |
| Maximum thicknes of console | 6mm |
| Ambient temperature for version | N/2: -15...+30oC W/3: -30...+50oC |
| Type of working:
- for lamps with bulbs - for lamps with LEDs |
discontinuous (possible continuous work with bulbs up to 2W) 2W |
| Product consistent with standard PN - EN 60947-1 | |
Notice:
When lamps with LEDS are connected with long wires, then is possible phenomenon of slight shining without supply voltage. This is result of induced voltages in long wires going along wires conducting high currents. To avoid this phenomenon one should disconnect both terminals of signaling lamps.